摘要
为提高对大电流接地开关设计结构的认识,提高设计可靠性,文中对某型号发电机断路器成套装置用接地开关进行了设计研究。接地开关体积小,动热稳定性考核严苛,采用经验公式与仿真分析相结合的方法,完成了满足短时耐受电流130 kA(3 s)、峰值耐受电流390 kA参数条件的接地开关设计,并通过动热稳定型式试验验证了设计的合理性和可靠性。
For improving the understanding of design structure of high current earthing switch and enhancing the design reliability,the design of earthing switch for a complete set of generator circuit breaker is studied.The earthing switch is small in size,and its peak and short-time withstand current type tests are severe.The design of the earthing switch meeting short-time withstand current of 130 kA(3 s)and peak withstand current of 390 kA is completed by combination of empirical formula and simulation analysis.The rationality and reliability of the design are verified by peak and short-time withstand current type tests.
作者
弟泽龙
程立
吕军玲
朱凯
马冲
DI Zelong;CHENG Li;LYU Junling;ZHU Kai;MA Chong(Xi’an XD Switchgear Co.,Ltd.,Xi’an 710077,China)
出处
《高压电器》
CAS
CSCD
北大核心
2023年第6期202-207,共6页
High Voltage Apparatus
关键词
接地开关
发电机断路器
大电流
动热稳定
可靠性
earthing switch
generator circuit breaker
high current
peak and short-time withstand current
reliability
作者简介
弟泽龙(1988—),男,硕士,工程师,从事发电机断路器系列高压开关研发设计(E-mail:dizlong0420@163.com);程立(1971—),男,本科,教授级高级工程师,从事发电机断路器系列高压开关研发设计;吕军玲(1982—),男,硕士,高级工程师,从事发电机断路器系列高压开关研发设计;朱凯(1989—),男,博士,工程师,从事高压开关研发设计;马冲(1986—),女,硕士,工程师,从事发电机断路器系列高压开关研发设计。