摘要
针对某330 kV变电站户外高压隔离开关支座开裂现象,进行了详细的全面检测与分析,深入研究后发现应力腐蚀的发生是导致支座开裂的主要原因,最后提出了加装隔离护罩,加大巡检力度、加强腐蚀监测等,防护措施与建议。
In response to the phenomenon of cracking of outdoors high-voltage disconnector holder in a 330 kV substation,this paper carries out detailed tests and analysis,the in-depth studies show that the main cause of the cracking of outdoors high-voltage disconnector holder is the occurrence of stress corrosion.Finally,the paper puts forward the corresponding protective measures and suggestions,such as add shielding,stengthen inspection efforts and enhance corrosion moitoring.
作者
李军
李炜
高世刚
姜梅
LI Jun;LI Wei;GAO Shigang;JIANG Mei(Lanzhou City University,Lanzhou 730070;Electric Power Research Institute of State Grid Gansu Electric Power Co.,Ltd.,Lanzhou 730070)
出处
《电力安全技术》
2020年第12期30-32,共3页
Electric Safety Technology
关键词
高压隔离开关
支座
开裂
应力腐蚀
high-voltage disconnector
holder
cracking
stress corrosion