期刊文献+

典型工业区输电线路金具腐蚀失效分析 被引量:30

Corrosion Failure of Fittings in Electric Power Transmission Line in Typical Industrial Areas
原文传递
导出
摘要 对某500 kV输电线路金具腐蚀试样进行力学实验、XRD分析、SEM分析和电化学测试,研究了典型工业区金具的腐蚀机理。结果显示,S是引起金具腐蚀的关键因素,通过形成可溶性硫酸盐促进了镀锌保护膜的消耗,另外拉应力和微动腐蚀也对金具腐蚀有影响。结合广西、湖南地区的酸雨数据和金具腐蚀情况验证了该结论,提出了工业区金具的防护措施。 Failed fitting samples of a 500 kV electric power transmission line was investigated by means of mechanical property test, electrochemical test, as well as SEM and XRD characterization. The results show that sulfur is the critical factor of fittings corrosion. It forms soluble sulfate to con- sume zinc coatings faster. Furthermore, tensile stress and fretting corrosion also affect the fittings corrosion. The conclusions coincide fairly well with the service situations of fittings in terms of ac- id rain and corrosion in the relevant areas of Guangxi and Hunan province. Then anti-corrosion measures for fittings in industrial areas are proposed.
出处 《腐蚀科学与防护技术》 CAS CSCD 北大核心 2013年第6期508-513,共6页 Corrosion Science and Protection Technology
基金 国家电网公司总部科技项目(KG12K16004)资助
关键词 金具 输电线路 腐蚀 失效 fitting, power transmission line, corrosion, failure
作者简介 陈军君,男,1982年生,工程师,硕士,研究方向为电网输变电材料、材料保护 通讯作者:陈军君,E—mail:chengjie0082@163.com