气液分离器高频异常噪声分析与改善

Analysis and improvement of high-frequency abnormal noise of gas-liquid separator
在线阅读 下载PDF
导出
摘要 针对空调器室外机气液分离器出现1 208 Hz异常噪声的问题,基于模态测试与仿真理论,对气液分离器的内部管路进行模态测试与仿真分析。研究结果表明:该异常噪声由气液分离器的固定板与内部管路局部共振引起;模态测试与仿真的固有频率仅差6 Hz,且模态振型一致,说明有限元模型准确性高,可用于指导方案的优化设计,缩短验证周期;固定板采用翻边设计,且内部管路薄弱部位增加2块固定板,气液分离器的固有频率可以有效避开1 208 Hz的激振频率,使室外机的噪声值从67.6 dB(A)降低至66.5 dB(A),1 208 Hz频率下的噪声峰值从60.76 dB(A)降至35.46 dB(A),高频异常噪声消失,改善显著。 Aiming at 1 208 Hz abnormal noise from the gas-liquid separator of the outdoor unit of the air conditioner,based on the modal test and simulation theory,the modal test and simulation analysis of the internal pipeline of the gas-liquid separator are carried out.The study results show that the abnormal noise is caused by the local resonance of the fixed plate and the internal pipeline.The natural frequency difference between modal test and simulation is only 6 Hz,and the modal shapes are consistent.The finite element model has high accuracy,which can be used to guide the optimization of the scheme and shorten the verification cycle.The fixed plate adopts flanging design,and two fixed plates are added at the weak part of the internal pipeline.The natural frequency of the gas-liquid separator effectively avoids the excitation frequency of 1 208 Hz.So that the noise value of the outdoor unit is reduced from 67.6 dB(A) to 66.5 dB(A),and the peak value at 1 208 Hz is reduced from 60.76 dB(A) to 35.46 dB(A).The high-frequency abnormal noise disappears and the improvement effect is significant.
作者 杜明龙 徐坤 姜志成 徐亚男 李钟昀 Du Minglong;Xu Kun;Jiang Zhicheng;Xu Ya'nan;Li Zhongyun(Qingdao Hisense Hitachi Air-conditioning Systems Co.,Ltd.)
出处 《制冷与空调》 2024年第7期23-26,共4页 Refrigeration and Air-Conditioning
关键词 空调器 室外机 气液分离器 噪声 模态 仿真 优化 air conditioner outdoor unit gas-liquid separator noise modal simulation optimization
作者简介 杜明龙,硕士,高级工程师,主要从事空调减振降噪方面的研究。
  • 相关文献

参考文献10

二级参考文献60

共引文献45

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部