摘要 采用有限时间热力学、㶲方法分析了水冷多联热管系统(MSHPS)。计算结果表明,IT服务器应该集中安排在1.3m以下的位置。CDU在6s的时间内具有约74J的传热量。最佳流量时CDU的速率为0.82kg/s。计算了免费冷却时间,部分免费冷却时间。并分析了中国主要城市的节能潜力从61%到25%。研究结果对其他管网系统实际应用具有重要意义。 Thefinite time thermodynamic analysis,the exergy method were employed to build the simulation model of the combined system of water cooled multi-spilit heat pipe system(MSHPS)used in data center.The results show that the IT servers should concentrate on arranging at the location below 1.3 m.The CDU has a heat transfer of about 74 J in a period of 6 s.And the optimumflow rate of the CDU is 0.82 kg/s.Then the free cooling time,part time free cooling and energy saving potential in major cities of China were analysised.The energy saving potential is from 61%to 25%.The results are of great significance for the operational control and practical application of other pipe-net systems.
作者 杨志新 陈飞虎 刘杰宏 徐寒婷 Yang Zhixin;Chen Feihu;Liu Jiehong;Xu Hanting
出处 《洁净与空调技术》 2024年第1期28-33,共6页 Contamination Control & Air-Conditioning Technology
关键词 有限时间热力学分析 数据中心 热管空调系统 制冷剂流量分布特性 节能潜力 Finite time thermodynamic analysis Exergy method IDC room Heat pipe air-conditioning system SIMULINK software Refrigerantflow distribute characteristic Energy saving potential
作者简介 杨志新,男,1958年11月生,本科,工程师;通信作者:陈飞虎,410082湖南省长沙市岳麓区岳麓西大道588号芯城科技园6栋7层,18874174221,E-mail:maxxom121@163.com。