摘要
对新疆某数据中心水侧蒸发冷却空调系统进行了监测,分析了蒸发冷却冷水机组间接段、淋水填料段性能随环境参数变化的规律,得到了不同工况下系统运行模式的切换条件。夏季典型日测试结果显示,机组出水温度为13.1~16.9℃,冷源系统冬季能效比为14.8,春夏秋季能效比为7.3。
Monitors the water-side evaporative cooling air conditioning system of a data center in Xinjiang,analyses the law of the performance of the indirect section of the evaporative cooling chiller and the water filling section with environmental parameters,and obtains the switching conditions of the system operation mode under different working conditions.Test results on a typical day in summer show that the outlet water temperature of the unit is 13.1 to 16.9℃,the energy efficiency ratio of the cold source system in winter is 14.8,and the energy efficiency ratio in spring,summer and autumn is 7.3.
作者
田振武
黄翔
褚俊杰
金洋帆
Tian Zhenwu;Huang Xiang;Chu Junjie;Jin Yangfan(Xi’an Polytechnic University,Xi’an,China;不详)
出处
《暖通空调》
2021年第8期12-17,共6页
Heating Ventilating & Air Conditioning
基金
“十三五”国家重点研发计划项目(编号:2016YFC0700400)。
关键词
干燥地区
数据中心
水侧蒸发冷却
完全自然冷却
运行测试
系统适用性
dry zone
data center
water-side evaporative cooling
completely natural cooling
operation test
system applicability
作者简介
田振武,男,1994年7月生,在读硕士研究生,710600陕西省西安市临潼区陕鼓大道58号,西安工程大学城市规划与市政工程学院,E-mail:936391028@qq.com。