针对某核电厂3号机组6.6 kV配电系统断路器无法分闸的问题,对断路器的扭簧位置、油脂干枯情况等进行分析,结果表明断路器分闸驱动机构卡涩是故障的根本原因,据此制定了针对性的处理措施并优化维修策略。
In view of the problem that the circuit breaker of 6.6 kV distribution system of unit 3 in a nuclear power plant cannot be opened,the position of the torsion spring of the circuit breaker and the situation of grease drying are analyzed.The results show that the jamming of the opening driving mechanism of the circuit breaker is the root cause of the fault.Based on this,targeted treatment measures and maintenance strategy are formulated.
作者
孙立国
梁修华
朱小灿
SUN Li-guo;LIANG Xiu-hua;ZHU Xiao-can(China Nuclear Power Operations Co.Ltd.,Shenzhen 518124,China)
出处
《中小企业管理与科技》
2020年第18期153-154,共2页
Management & Technology of SME
关键词
断路器
分闸
卡涩
扭簧
circuit breaker
opening
jam
torsional spring
作者简介
孙立国(1986-),男,内蒙古通辽人,工程师,从事核电厂配电盘检修及大修准备研究。