摘要 To alleviate the heavy load of massive alarm on operators, alarm threshold in chemical processes was optimized with principal component analysis(PCA) weight and Johnson transformation in this paper. First, few variables that have high PCA weight factors are chosen as key variables. Given a total alarm frequency to these variables initially, the allowed alarm number for each variable is determined according to their sampling time and weight factors. Their alarm threshold and then control limit percentage are determined successively. The control limit percentage of non-key variables is determined with 3σ method alternatively. Second, raw data are transformed into normal distribution data with Johnson function for all variables before updating their alarm thresholds via inverse transformation of obtained control limit percentage. Alarm thresholds are optimized by iterating this process until the calculated alarm frequency reaches standard level(normally one alarm per minute). Finally,variables and their alarm thresholds are visualized in parallel coordinate to depict their variation trends concisely and clearly. Case studies on a simulated industrial atmospheric-vacuum crude distillation demonstrate that the proposed alarm threshold optimization strategy can effectively reduce false alarm rate in chemical processes. To alleviate the heavy load of massive alarm on operators, alarm threshold in chemical processes was optimized with principal component analysis(PCA) weight and Johnson transformation in this paper. First, few variables that have high PCA weight factors are chosen as key variables. Given a total alarm frequency to these variables initially, the allowed alarm number for each variable is determined according to their sampling time and weight factors. Their alarm threshold and then control limit percentage are determined successively. The control limit percentage of non-key variables is determined with 3σ method alternatively. Second, raw data are transformed into normal distribution data with Johnson function for all variables before updating their alarm thresholds via inverse transformation of obtained control limit percentage. Alarm thresholds are optimized by iterating this process until the calculated alarm frequency reaches standard level(normally one alarm per minute). Finally,variables and their alarm thresholds are visualized in parallel coordinate to depict their variation trends concisely and clearly. Case studies on a simulated industrial atmospheric-vacuum crude distillation demonstrate that the proposed alarm threshold optimization strategy can effectively reduce false alarm rate in chemical processes.
出处 《Chinese Journal of Chemical Engineering》 SCIE EI CAS CSCD 2018年第8期1653-1661,共9页 中国化学工程学报(英文版)
基金 Supported by the National Natural Science Foundation of China(21576143)
关键词 Alarm threshold Chemical process PCA Johnson transformation Variable weight 优化策略 化学过程 约翰逊 PCA 警报 阈值 重量 控制限
作者简介 Wende Tian,E-mail address:tianwd@qust.edu.cn
  • 相关文献

同被引文献45

引证文献4

二级引证文献12

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部