期刊文献+

母线倒负荷引发电容器自爆的暂态过程仿真分析 被引量:1

Analysis and Simulation on the Transient Process of Self-explosion of Capacitor Group Caused by the RearrangementOperation of Bus Load
在线阅读 下载PDF
导出
摘要 以某变电站为例,采用电力系统暂态仿真程序ATP/EMTP,对母线倒负荷引发电容器自爆的暂态过程进行仿真分析,并采取相应的措施来预防暂态电压引发电容器自爆事故。分析结果表明,不带电容器进行母线倒负荷操作,可避免电容器所接母线电压过高,防止电容器在操作过程中引发过大电流而发生自爆危险。 Taking a substation as an example, the power system transient simulation program ATP / EMTP was used to simulate the transient process of self-explosion of capacitor group caused by the rearrangement operation of bus load. The corresponding measures were taken to prevent and solve the accident of capacitor self-explosion caused by transient voltage. Analysis results showed that it can avoid the over voltage of the bus and prevent over current caused by the operation of capacitors without the capacitor for by the rearrangement operation.
作者 周开涛 ZHOU Kaitao(State Grid Xin Yuan Co. , Ltd. , Beijing 100053, China)
出处 《电工技术》 2018年第7期97-99,共3页 Electric Engineering
关键词 母线 倒负荷 电容器 自爆 暂态过程 仿真 bus load rearrangement capacitor self-explosion transient process simulation
  • 相关文献

参考文献1

二级参考文献18

  • 1Joubert C. Etude des phenomenes electromagnetiques dans les condensateurs a films metallises-nouvelles generation de ondensateurs[D]. Lyon, France: Ecole Centrale de Lyon, 1996.
  • 2Macdougall F, Ennis J, Xiao Hui Yang, et al. Large high energy density pulse discharge capacitor characterization[C]. IEEE 2005 Pulsed Power Conference. California, USA, 2005: 1215- 1218.
  • 3Agarwal V K. Aging of multistressed polymeric insulators[J]. IEEE Trans on Electr Insul, 1989, 24(3) : 741-764.
  • 4Reed C W, Cichanowski S W. The fundamentals of aging in hv polymer-film capacitors[J]. IEEE Trans on Dielectr Electr Insul, 1994, 1(6): 904-922.
  • 5Sarjeant W J, MacDougall F W, Larson D W, et al. Energy storage capacitors, aging, and diagnostic approaches for life validation[J]. IEEE Trans on Mag, 1997, 33(12): 501-506.
  • 6Nash J L. Biaxially oriented polypropylene film in power capacitors[J]. Polymer Eng Sci, 1988, 28(4): 862-870.
  • 7Lee Y D, Phillips P J. The electrically ruptured area of crosslinked polyethylene[J]. IEEE Trans on Electr Insul, 1991, 26 (7): 171-177.
  • 8Sanden B, Ildstad B. DC electrical and mechanical characterisation of polypropylene film[C]. IEEE Intern Conf on Conduction Breakdown in Solid Dielectrics. Vasteras, Sweden, 1998: 210- 213.
  • 9Gadoum A, Gosse B, Gosse J P. Accelerated ac degradation of impregnated PP films[J]. IEEE Trans on Dielectr Electr Insul, 1995, 2(8): 1075-1082.
  • 10Schneuwly A, Groning P, Schlapbach L, et al. Breakdown behaviours of oil impregnated polypropylene as dielectric in film apacitors[J]. IEEE Trans on Dielectr Electr Insul, 1998, 5 (11): 862-868.

共引文献5