摘要
针对设置双蓄热水箱的集中式太阳能热水系统,以辅助热源能耗为目标,分析了不同贮热水箱容积的设置对系统辅助热源能耗的影响。并通过运用TRNSYS软件,建立动态分析模型,比较分析了不同太阳能保证率条件下,单位面积集热器对应的贮热水箱容积对系统性能的影响。分析结果表明:单位面积集热器对应的蓄热水箱容积最优值分布在50~70 L/m^2范围内;贮热水箱的容积对系统能耗的影响较小,在单位面积集热器对应的蓄热水箱容积为40~100 L的推荐值范围内,其辅助热源的最大值与最小值差异在1%以内。
In order to improve the auxiliary heat source performance of the centralized hot water system with double storage tanks, the effect of the volume of storage tank per solar collector area in different solar fraction was analyzed by building dynamic simulation models with TRNSYS. Results indicated that : the optimal volume value of storage tank per solar collector area is in the numerical range 5070 L/m2. In addition, the influence of the storage tank volume on the energy consumption is very small and with the tank volume changing from 40 L/m2 to 100 L/m2, the largest difference is within 1%.
出处
《建筑节能》
CAS
2017年第2期35-38,共4页
BUILDING ENERGY EFFICIENCY
基金
"十二五"国家科技支撑计划课题(2014BAJ01B02):可再生能源利用建筑一体化设计研究与示范
关键词
太阳能热水系统
贮热水箱容积
系统优化
模拟分析
solar domestic hot water
storage tank v o l u m e
system optimization
simulation analysis
作者简介
刘剑(1987),男,上海人,毕业于上海交通大学,硕士,工程师,研究方向:建筑节能及可再生能源应用研究(liujian101215@126.com)