TN系统过电流保护电器兼作间接接触防护电器灵敏度校验实例 被引量:1

Example of Electrical Sensitivity Calibration of Over Current Protection Appliance Used as Indirect Protection in TN System
在线阅读 下载PDF
导出
摘要 结合某地下建筑排风机供电设计实例,从实际计算的角度探讨了TN系统过电流保护电器兼作间接防护电器时有关灵敏度校验的问题。提出对于远距离供电线路,利用过电流保护电器兼作间接防护电器的做法并不能达到保护要求,须重视保护灵敏度的校验,并通过加装剩余电流保护器,以便在发生接地故障时及时切除故障。 Combining by the power supply design of exhaust fan in an underground building,from the actual computational perspective,this paper discussed the sensitivity calibration problem of overcurrent protection appliances used as indirect protection in TN system. It is pointed out that the practice of overcurrent protection appliances used as indirect protection cannot meet the protection requirements for the long-distance power supply line,which should pay attention to the calibration of protection sensitivity. The residual current protector is equipped in order to timely remove the fault when the grounding fault happens.
作者 陈剑峰
出处 《现代建筑电气》 2016年第4期33-34,55,共3页 Modern Architecture Electric
关键词 接地故障 过电流保护电器 相保阻抗 灵敏度 grounding fault overcurrent protection device phase-protection impedance sensitivity
作者简介 陈剑峰(1986-),男.工程师。从事供配电系统设计工作。
  • 相关文献

参考文献4

  • 1低压配电设计规范:GB50054--5011[S].
  • 2中国航空工业规划设计研究院.工业与民用配电设计手册[M].3版.北京:中国电力出版社,2005.
  • 3GB50055-2011,通用用电设备配电设计规范[S].
  • 4民用建筑电气设计规范:JGJ16-12008[S].