摘要
本文结合天津市图书馆新馆地板送风空调系统,对其所采用的地板静压箱旋流送风口送风量特性进行了实验研究。通过搭建实验台和进行实验测试,获得了该类型送风口在不同送风量下风口内空气静压数据,整理并给出了地板静压箱旋流送风口送风量与风口内空气静压的关系,进而提出了一种用于该旋流送风口的现场风量测量的简易方法。
Combining with the Under-Floor Air Distribution (UFAD) system in the Tianjin New Library, field experiments on the characteristic of the volume of UFAD system' s air distributor were carried. By creating the test-bed and conducting an experiment, the experiment data of inner static air pressure corresponding to the different volume of air distributor was gotten. Then, the relationship between the volume and inner static air pressure of the UFAD system' s air distributor was analyzed. A simple field test method was put forward, which is used for field testing the air volume of the swirling air diffuser.
出处
《建筑热能通风空调》
2016年第2期76-78,83,共4页
Building Energy & Environment
关键词
地板送风空调系统
静压箱
旋流风口
送风量
现场测量
under-floor air distribution system, plenum chamber, swirling air diffuser, air supply volume, field test
作者简介
马江辉(1987-),男,硕士研究生;天津市西青区天津城建大学能源与安全工程学院(300384);E-mail:mjh_nuantong@126.com