期刊文献+

应用于太阳能集热再生系统的除湿效率模型 被引量:4

Dehumidification efficiency model for solar thermal regeneration system
在线阅读 下载PDF
导出
摘要 溶液除湿装置是太阳能空气预处理分级溶液集热/再生系统的重要组成部分,预测填料预除湿器空气出口参数变化是这种新型溶液再生系统设计时必须考虑的。文章通过定义湿度效率和等焓率预测填料型溶液除湿器的空气出口参数,采用实验和理论相结合的方法,分析影响湿度效率和等焓率变化的因素。发现当液气比小于2.0时,溶液和空气入口参数变化对湿度效率影响显著;溶液和空气入口温度对等焓率影响大;随液气比增加,湿度效率增加,等焓率下降。文章最后通过线性拟合方法得到湿度效率和等焓率的数学表达式,为太阳能空气预处理分级溶液集热再生系统理论建模提供理论基础。 Solar liquid desiccant air-conditioning system has attracted many attentions because of low-energy consumption,and solar liquid regenerator is one of important units in that system. A novel solar liquid regenerator designed by the author is the solar air-pretreatment solution grading collector/regenerator. The proposed liquid regeneration system needs a packed bed dehumidifier, and the prediction of outlet parameters of air in that dehumidifier must be considered for the design of the novel solar liquid regeneration system. A structured packing dehumidifier was designed and the systemic experiments were made at Southeast University in Nanjing, China in 2009. The structured packing dehumidifier has the size of 0.5 m(width)× 0.5 m(height)×0.3 m(length) with cross-flow mode. In order to increase flow rate of desiccant solution, instead of injecting directly strong solution into the interior of packed bed, a circulation solution pump was used for supplying solution for the dehumidifier. At the same time, a water-cooled heat exchanger was used to cool circulating solution in advance to control inlet temperature of solution. The experiments were performed under varying conditions including varying flow rates of air and solution and their inlet parameters. However, because of single structure of the experimental unit and limited variation range of experimental parameters, a method of numerical stimulation was used in this paper to study the effects of the inlet parameters of solution and air and the structure parameters of packing on the humidity effectiveness and the isenthalpic effectiveness. The previously experimental data were used to validate numerical model. For this purpose, several assumptions in physics were made, which were followed by the models of cross-flow dehumidification. The numerical simulation showed that as the concentration of Li Cl solution increased from 0.29 to 0.34 kg/kg, the humidity effectiveness was increased by 2.6% ~4.7% and the isenthalpic effectiveness was reduced by 20% ~30%. As the inlet temperature of solution rose from 15 to 25 ℃, the humidity effectiveness went up, especially when the liquid-gas ratio was less than 1.0. As for isenthalpic effectiveness, the solution inlet temperature had large impact on it and when the inlet temperature of solution was less than that of air, the isenthalpic effectiveness was negative. As the air humidity ratio at the inlet dropped from 12.3to 9.6 g/kg, the humidity effectiveness was increased by 2%~10% and the isenthalpic effectiveness was increased by about0.3. The higher inlet temperature of airflow yields the lower humidity effectiveness, and when the liquid-gas ratio is low, the effect of air's inlet temperature on humidity effectiveness is high. The effect of air's inlet temperature on isenthalpic effectiveness is similar to solution's inlet temperature, which shows when the inlet temperature of air is higher than that of solution, the isenthalpic effectiveness is negative and otherwise it is positive. As the product of area per unit volume and length of air flow channel increased from 110 to 180, the humidity effectiveness was increased by about 0.1, however, the isenthalpic effectiveness was basically unchanged. Therefore, the humidity effectiveness increases with the increasing of the inlet temperature, the concentration of solution, the area per unit volume as well as the length of air flow channel, and decreases with the increase in humidity ratio and air temperature at the inlet. The isenthalpic effectiveness is affected dramatically by inlet temperatures of air and solution. Structure parameters of packing have little effect on the isenthalpic effectiveness. Moreover, with the increasing of the liquid-gas ratio, the humidity effectiveness increases and the isenthalpic effectiveness decreases. Finally, 2 equations about humidity effectiveness and isenthalpic effectiveness were obtained by applying a nonlinear regression to rearrange numerical simulation results, which provide the theoretical basis for the modeling of solar air-pretreatment solution grading collector/regenerator.
出处 《农业工程学报》 EI CAS CSCD 北大核心 2016年第1期206-211,共6页 Transactions of the Chinese Society of Agricultural Engineering
基金 国家自然科学基金项目(51266010) 江西省科技支撑计划项目(20123BBG70195)
关键词 模型 太阳能 溶液除湿 湿度效率 等焓率 液气比 models solar liquid desiccant dehumidification humidity effectiveness isenthalpic effectiveness ratio of flowrate of solution to air
作者简介 彭冬根(1975-),男,博士,副教授,主要从事太阳能制冷空调研究,南昌南昌大学建筑工程学院,330031。Email:ncu_hvac2013@163.com
  • 相关文献

参考文献25

  • 1Armanasco F,Colombo L P M,Lucchini A,et al.Performance analysis of a solar cooling plant based on a liquid desiccant evaporative cooler[J].International Journal of Refrigeration,2015,53:163-176.
  • 2Mohaisen A K,Ma Z.Development and modelling of a solar assisted liquid desiccant dehumidification air-conditioning system[J].Building Simulation,2015,8(2):123-135.
  • 3Qi Ronghui; Lu Lin; Huang Yu.Energy performance of solar- assisted liquid desiccant air-conditioning system for commercial building in main climate zones[J].Energy Conversion and Management,2014,88:749-757.
  • 4Abdel-Salam A H,Ge G,Simonson C J.Thermo-economic performance of a solar membrane liquid desiccant air conditioning system[J].Solar Energy,2014,102:56-73.
  • 5Cheng Qing,Zhang Xiaosong.Review of solar regeneration methods for liquid desiccant air-conditioning system[J].Energy and Buildings,2013,67:426-433.
  • 6Elsarrag E.Evaporation rate of a novel tilted solar liquid desiccant regeneration system.Solar Energy,2008,82(7):663-668.
  • 7Qi Ronghui,Lu Lin,Yang Hongxing,et al.Investigation on wetted area and film thickness for falling film liquid desiccant regeneration system[J].Applied Energy,2013,112:93-101.
  • 8Zhang L,Hihara E,Matsuoka F,et al.Experimental analysis of mass transfer in adiabatic structured packing dehumidifier/ regenerator with liquid desiccant[J].International Journal of Heat and Mass Transfer,2010,53(13-14):2856-2863.
  • 9Bassuoni M M.An experimental study of structured packing dehumidifier/regenerator operating with liquid desiccant[J].Energy,2011,36(5):2628-2638.
  • 10Fumo N,Goswami D Y.Study of an aqueous lithium chloride desiccant system:air dehumidification and desiccant regeneration[J].Solar energy,2002,72(4):351-361.

二级参考文献8

  • 1张旭,博士学位论文,1997年
  • 2Liu X H,Zhang Y, Qu K Y. Experimental study on mass transfer performances of cross flow dehumidifier using liquid desiccant [ J]. Energy Conversion and Management, 2006,47 ( 15/16 ) : 2682-2692.
  • 3Ren Chengqin, Jiang Yi, Zhang Yinping. Simplified analysis of coupled heat and mass transfer processes in packed bed liquid desiccant-air contact system [ J ], Solar Energy, 2006,80 ( 1 ) : 121-131.
  • 4Elsarrag E, Ali Elsheikh E M, Jain Sanjeev. Mass transfer correlations for dehumidification of air by Triethylene Glycol in a structured packed column [ J ]. Industrial and Engineering Chemistry Research.2004. 39:7676-7681.
  • 5Chung T W, Ghosh T K, Hines A L . Comparison between random and structured packings for dehumidification of air by lithium chloride solution and their heat and mass transfer correlations [ J ]. Industrial and Engineering Chemistry Research, 1996, 35 ( 1 ) : 192-198.
  • 6Yonggao Yin, Xiaosong Zhang. A new method for determining coupled heat and mass transfer coefficients between air and liquid desiccant[ J]. International Journal of Heat and Mass Transfer , 2008,51 : 3287-3297.
  • 7张欢,李春茹,李博佳.金属填料型吸收式除湿器的除湿性能研究[J].暖通空调,2009,39(9):46-50. 被引量:6
  • 8张海江,柳建华,张良,高文忠,杨建超,朱立伟.叉流除湿器传质性能实验研究[J].制冷学报,2010,31(6):21-27. 被引量:15