期刊文献+

地下车库自动喷水强度数值模拟研究 被引量:6

Underground garage automatic sprinkler density numerical simulation research
在线阅读 下载PDF
导出
摘要 根据单辆车热释放速率峰值为8 MW的参考曲线,对地下车库一个存车单元3个车位的火灾场景进行FDS数值模拟。对比模拟国内外规范规定的不同自动喷水强度下的辐射热、热释放速率、温度等的变化情况。结果表明,无自喷时可发生火灾蔓延,有自喷时随着喷水强度的增大辐射热减小,控火时间缩短,温度下降加快。综合考虑控灭火可靠性和经济性,建议设计喷水强度为6.0L/(min·m2)。 The underground garage fire were simulated by FDS based on the reference curve which peak heat release rate of sin gle burning car was 8 MW. The fire scene was a parking unit with 3 parking lots. The radiant heat, heat release rate and temperature changes with different automatic sprinkler densities from domestic and foreign garage criterions were compared. It was found that fire could spread without sprinkler; the radiant heat decreased, fire control time became shorter and the tern peralure dropped faster with the increase of sprinkler density. Considering reliability of fire control and suppression and econ omy, density design parameter of 6.0 L/(min · m2 ) is recom mended.
出处 《消防科学与技术》 CAS 北大核心 2016年第1期80-84,共5页 Fire Science and Technology
关键词 车库火灾 喷水强度 辐射热 热释放速率 控火时间 garage fire sprinkler density radiant heat heat re lease rate fire control time
作者简介 王东勋(1989-),女,北京建筑大学环境与能源工程学院硕士研究生,主要从事消防理论与技术方面研究,北京市西城区展览馆路1号,100044。
  • 相关文献

参考文献11

  • 1I.i Y. Assessment of vehicle fires in New Zealand parking buildings [D]. New Zealand: University of Canterbury,2004.
  • 2程远平,R John.小汽车火灾试验研究[J].中国矿业大学学报,2002,31(6):557-560. 被引量:64
  • 3宋波,赵力增,白殿涛,智会强,王海娟,王健强,田立伟,罗宗军,张君娜,刘欣.普通轿车燃烧特性的试验研究[J].中国安全科学学报,2013,23(7):26-31. 被引量:11
  • 4Deckers X, Haga S, Sette B, etal. Smoke control in case of fire in alarge car park: Full scale experiments[J]. Fire Safety Journal, 2013,57:11-21.
  • 5姜立春,宋敏丽,陈锦添.地下复式车库火灾风险研究[J].消防科学与技术,2014,33(9):1015-1018. 被引量:5
  • 6Janssens M. Development of a database of full scale calorimeter tests of motor vehicles[R]. Washington: SAE Technical Paper, 2007.
  • 7Schleieh J B, Caiot L G, Pierre M, et al. Development of design rules for steel structures subjected to natural fires in closed car parks[R]. Luxembourg:CEC. 1999.
  • 8ThomasP H. Design guide: Structure fire safety CIBW14 Work shop report[J]. Fire Safety Journal. 1986,10(2) :77- 137.
  • 9陈阵,王霁,张苗,吴欣田,张哲源.地下车库火灾荷载计算模型的建立与应用研究[J].安全与环境工程,2014,21(4):127-131. 被引量:5
  • 10GB50067-97.汽车库、修车库、停车场设计防火规范[S].[S].,..

二级参考文献25

  • 1吴凤,邓军.地下商业街火灾烟气流动实验研究[J].中国安全科学学报,2005,15(12):60-63. 被引量:18
  • 2贾春芬,姚会兰,路世昌,智会强.地下停车库火灾风险性的评价研究[J].火灾科学,2006,15(1):6-10. 被引量:12
  • 3徐亮,张和平,杨昀,王蔚,朱五八.废旧轮胎全尺寸火灾实验研究[J].应用基础与工程科学学报,2006,14(1):33-39. 被引量:7
  • 4许彬,张永明,刘申友,方俊.轮胎的全尺寸火灾实验研究[J].热科学与技术,2006,5(2):163-167. 被引量:3
  • 5[1]John R. Gutachten ueber die Bemmesung und Wirksamkait von Rauch-und Waermeabzugsanlagen fuer unterirdische Garagen [R]. Forschungsstelle fuer Brandschutztechnik an der Universitaet Karlsruhe (TH). Dezember 1986:1-37.
  • 6[2]Schwarz C, Kolb T.Verwendung von Brandsimulationsrechnungen fuer Sicherheitsmagnet in Tunnelanlagen und unterirdischen Verkehrsanlage [J]. vfbd-Zeitschrift Forschung, Technik und Management im Brandschutz,2001,50(1):29-39.
  • 7[3]Steinert C. Messung und Simulation von Fahrzeugbraenden in Tunneln[D],Dissestation vom Fachbereich fuer Bauingenieur-und Vermessungswesen der TU Braunschweig,1995.
  • 8[4]ISO 5660-1.Fire tests-Reaction to fire-Rate of heat release from building products [S],First edition (1993).
  • 9[5]ISO 9705. Fire tests-Full-scale room test for surface products[S],First edition (1993).
  • 10[6]Schneider U, Lebeda C, Max U.Entrauchung von grossen Geschossflaechen und unterirdischen Parkdecks [J].vfdb-Zeitschrift Forschung,Technik und Management im Brandschutz,1994,43(4):138-149.

共引文献227