摘要 输电线路遭受非故障性雷击可能会造成行波保护误动。针对该问题,通过分析短路故障、故障性雷击及非故障性雷击产生的附加电流分量的特征,提出利用基波电流相量变化率快速识别雷击干扰的方法。线路发生短路故障或遭受故障性雷击,附加电流分量中的衰减直流分量和基波故障分量导致基波电流相量变化率迅速增大;线路遭受非故障性雷击,雷击后基波电流相量变化率较小。利用S变换确定雷击或故障的起始时刻,依据起始时刻之后基波电流相量变化率的大小识别雷击干扰。EMTDC仿真结果验证了所提方法的有效性和可靠性。 Travelling wave protection may operate improperly when transmission line is struck by lightning,aiming at which,a method applying the change rate of fundamental current phasor to rapidly identify the lightning disturbance is proposed. Analysis shows that,the decaying DC component and the fundamental fault component in the additional current induced by the short circuit fault or lightning-strike fault make the change rate of fundamental current phasor increasing rapidly while it keeps small when the lightning disturbance does not result in a fault. The start time of fault or lightning disturbance is confirmed by S transform and the change rate of the fundamental current phasor after it is used to identify the lightning disturbance. The simulative results by EMTDC prove the proposed method is effective and reliable.
出处 《电力自动化设备》 EI CSCD 北大核心 2015年第2期55-61,共7页 Electric Power Automation Equipment
基金 国家高技术研究发展计划(863计划)资助项目(2012-AA050208) 国家自然科学基金资助项目(51307145)~~
关键词 雷电 雷击干扰 行波保护 继电保护 输电 线路 基波电流 相量变化率 lightning lightning disturbance travelling wave protection relay protection electric power transmission electric lines fundamental current phasor change rate
作者简介 刘兴茂(1975-),男,四川南充人,博士研究生.主要研究方向为电力系统继电保护(E-mail:liuxingmao1@gmail.com); 林圣(1983-),男,湖南宁乡人,讲师.博士.主要研究方向为电力系统故障诊断、故障测距与继电保护 李小鹏(1987-),男,河南许昌人,博士研究生.研究方向为输电线故障测距与继电保护 何正友(1970-),男,四川自贡人,教授,博士研究生导师,博士,主要从事信号处理和信息理论在电力系统故障分析中的应用、新型继电保护原理、配网综合自动化等方面的研究工作
  • 相关文献

参考文献19

二级参考文献169

共引文献380

同被引文献175

引证文献10

二级引证文献54

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部