摘要 电气火灾是由非人为因素引起的,若能提前预警,则可有效避免火灾发生。传统电气火灾预警方法是对剩余电流幅值进行监测,其无法准确预警剩余电流引起的电弧电气火灾。对剩余电流电弧故障的特征信息进行了研究,提出了电弧型电气火灾的监测方法。该方法通过判断剩余电流高频信号峰值来进行调整,若超出整定值则预警。结果表明,该方法可克服传统监测法的漏报缺陷,提高预警系统的可靠性。 Electrical fire is not caused by human factors; it is possible to be effectively avoided by earlier warning. The traditional warning method is to monitor the amplitude of the residual current, it is unable to precisely forecast the arc-type electrical fire caused by residual current. Thus the feature information of the fault of residual current is researched, the proper monitoring method for arc-type electrical fire is proposed. This method makes the issue warning through judging the peak value of the high frequency signal of the residual current, and issue warning when it exceeds the setpoint. The result indicates that the method overcomes the under reporting defects and enhances the reliability of the fire warning system.
出处 《自动化仪表》 CAS 北大核心 2013年第6期16-19,共4页 Process Automation Instrumentation
基金 四川省教育厅科研基金资助项目(编号:12ZB004) 成都纺专科研基金资助项目(编号:2011fzlkB005)
关键词 电弧 电气火灾 剩余电流 介质损耗 故障预警 Arc Electrical fire Residual current Dielectric loss Fault warning
作者简介 第一作者王万岗(1975+),男,现为西南交通大学高电压与绝缘技术专业在读博士研究生,讲师;主要从事电接触与电弧理论方面的研究。
  • 相关文献

参考文献11

  • 1公安部消防局.中国火灾统计年鉴[G].北京:中国人事出版社.2006.
  • 2公安部消防局.中国火灾统计年鉴[G].北京:中国人事出版社.2007.
  • 3公安部消防局.中国火灾统计年鉴[G].北京:中国人事出版社.2008.
  • 4公安部消防局.中国火灾统计年鉴[G].北京:中国人事出版社.2009.
  • 5何瑞华.我国新一代低压电器发展与展望[J].低压电器,2012(1):1-6. 被引量:16
  • 6李奎,陆俭国,武一,岳大为,侯树民,袁金丽,张冠英.自适应漏电保护技术及其应用[J].电工技术学报,2008,23(10):53-57. 被引量:47
  • 7Brerman P V. Residual current device with high immunity to nuisance tripping circuits[J]. Devices and Systems ,IEEE ,1993(2) :140-144.
  • 8Li K, Wang Y, Wang J. Study on residual current protective strategy based on network [ C ]//IITAW, 2009 : 394-397.
  • 9臧桂丛.电气火灾监控系统对接地故障电弧性短路引起火灾的预防[J].消防技术与产品信息,2011,24(12):18-20. 被引量:6
  • 10Brown D W. Development of electric cables for fire situations [ J ]. Power Engineering Journal, 1997,11 ( 3 ) : 101 - 106.

二级参考文献12

  • 1刘连永,王宝华.自适应零序电流保护的研究[J].南京工程学院学报(自然科学版),2006,4(1):50-55. 被引量:7
  • 2Kidd A L, George H Scholes. Successful selection and operation of overcurrent and residual current protective measures[C]. Proceedings of the International Conference on Installation Engineering Designing and Maintaining Successful Systems, 1998: 50-57.
  • 3Nomura K, Hisalsune F, Yamada T. The present state and future trends in circuit breakers and earth leakage circuit breaker[J]. Mitsubushi Denki Giho(Japan) 1995, 9 (4): 2-6.
  • 4鲁文军,林湘宁,黄小波,刘沛,薄志谦.一种新的自适应突变量距离保护方案[J].电力系统自动化,2007,31(14):85-88. 被引量:4
  • 5GB50045-95(2005年版),高层民用建筑设计防火规范[S].
  • 6GB 50016-2006,建筑设计防火规范[S].
  • 7GB 13955-2005,剩余电流动作保护装置安装和运行[S].
  • 8GB14287-2005,电气火灾监控系统[S].
  • 9JGJ 16-2008 民用建筑电气设计规范[S].
  • 10葛耀中.自适应继电保护及其前景展望[J].电力系统自动化,1997,21(9):42-46. 被引量:115