摘要
随着风电装机容量的增长,风电场接入运行对电力系统稳定性的影响不容忽视。借助单机无穷大系统分析了双馈风电机组的自身稳定性,发现双馈感应发电机转子运动没有机电暂态失稳现象,但存在电磁暂态失稳现象;研究了双馈风电场与同步电机运行在典型接线方式下系统稳定性的差异和变化。仿真算例表明,由于双馈风电机组有功功率的快恢复特性,可能使含双馈风电场混合电力系统的暂态稳定水平显著降低。
The integration of large scale wind farm brings serious influence to the stability of power system.The stability of doubly-fed induction generator(DFIG) via single machine vs.infinite system is investigated at first.It is revealed that,for the rotor motion of DFIG itself,there exists the electromagnetic transition unstable phenomenon but not kinetic unstable phenomenon.Furthermore,according to the connection mode of DFIG-based wind farm and traditional synchronous generator,the transient stability of power system is compared and analyzed.Examples by simulation show that,due to the fast recovery character of the active power output by DFIG,the transient stability of hybrid system containing DFIG-based wind farm may be deteriorated obviously.
出处
《电力系统及其自动化学报》
CSCD
北大核心
2012年第1期133-137,共5页
Proceedings of the CSU-EPSA
关键词
双馈感应发电机
风电场
电力系统
暂态稳定性
doubly-fed induction generator
wind farm
power system
transient stability
作者简介
盛超(1972-),男,工程师,研究方向为电力系统分析及励磁控制。Email:sheng_chao@163.net
曾杰(1979-),男,工程师,研究方向为电力系统分析和新能源。Email:zjhust@gmail.com
郝正航(1972-),男,博士,研究方向为电力系统稳定和风力发电。Email:haozhenghang@163.com
曾沅(1975-),男,副教授,研究方向为电力系统安全性与稳定性。Email:zengyuan@tju.edu.cn