期刊文献+

含水树XLPE电缆ULSW—AC叠加电压激励响应 被引量:1

Excited Response of Water Treeing XLPE Cable Insulation by Superposition of U lira-low Square-wave and Power Frequency Voltage
在线阅读 下载PDF
导出
摘要 通过研究发现,在对XLPE电缆施加超低频方波的同时,再叠加一定大小的工频电压,使含有水材老化电缆绝缘的响应电流波形产生显著畸变,而对比空白电缆样品的响应电流波形基本不变;本文同时对这种叠加效应的产生机理进行了探讨。这种方法有可能发展成为XLPE电缆离线检测的有效手段。 It is found that when a superposition voltage ofultra-low square-wave and power frequency is applied to thewater treeing insulation of XLPE cable, the response current wave shape is greatly different from that of one withoutwater treeing.The formation mechanism of superpositionresponse is discussed in this paper. The method of superposition response could be developed to an efficiency means foroff-line diagnosis of XLPE cable insulation
机构地区 西安交通大学
出处 《高电压技术》 EI CAS CSCD 北大核心 1999年第2期21-24,共4页 High Voltage Engineering
基金 西安交通大学科学研究基金
关键词 XLPE电缆 水树老化 叠加响应 电压激励 试验 XLPE cable water-trees ultra-low squarewave superposition-response
  • 相关文献

参考文献3

二级参考文献2

共引文献22

同被引文献4

  • 1郑晓泉,曹晓珑.XLPE电缆护套电阻及接地化学电势对在线诊断的影响及其测量方法[J].电线电缆,1996(4):20-22. 被引量:11
  • 2 J L Chen,J C Filipini.The morphology and behavior of the water tree[J].IEEETransactions on EI,1993,28(2):271-286.
  • 3 Y Ikeda,N Hozumi. Deterioration diagnosis of 22-22KV XLPE cables by residualcharge measurement[A]. Proceedings of 1994 International Joint Conference:3rdJapan-China Conference on Electrical Insulation Diagnosis[C]1994..
  • 4C Shnoda,T Hashizume,et al.A consideration of DC leakage current peak in XLPECables[A].Proceedings of the international conference on properties and applications ofdielectric materials[C].Seoul, Korea:1997.