期刊文献+

基于移相原理不接地系统单相接地保护判据

Criteria of Single Phase Grounding Protection in Non-grounding System Based on the Phase-shift Principle
在线阅读 下载PDF
导出
摘要 分析了中性点不接地系统单相接地的电流量相量,获得了不接地系统发生金属性或经过渡电阻单相接地时线路电流的特点,提出了利用移相后将电流综合的不接地系统单相接地故障的判据。结果表明,该方法简单、有效、可靠、精度高,解决了出线回路少或线路短、利用比较电容电流判别单相接地的误判问题,可供借鉴。 The current phasor of single phase grounding in neutral non-grounding system is analyzed, and the characteristics of line current are also drawn when the metallic grounding or single phase grounding via transition resistance occurs in non-grounding system. Based on the phase shift, a criteria of single phase grounding fault is presented. The resuits show that this method has characteristics of simplicity, effectiveness, reliability and high precision. Thus, it solves the commission error problem caused by the few circuits of outgoing line or the short line length and discrimination single phase grounding by comparing the capacitance current.
出处 《水电能源科学》 北大核心 2010年第3期155-157,共3页 Water Resources and Power
关键词 移相原理 中性点不接地系统 金属性接地 经过渡电阻接地 电容电流 phase shift principle neutral non-grounding system metallic grounding grounding via transition resist- ante capacitance current
作者简介 张国良(1963-),男,副教授,研究方向为电力工程,E—mail:zgl0594@126.com 通讯作者:许建安(1950-),男,教授,研究方向为电力工程.E-mail:fjsyxja@126.tom
  • 相关文献

参考文献4

二级参考文献20

共引文献78

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部