冷却塔进风口加装导风板后的冷却性能比较与评价 被引量:14

Performance evaluation and its comparison of cooling towers before and after the installation of air deflectors
在线阅读 下载PDF
导出
摘要 针对冷却塔的冷却性能在很大程度上受外界侧风的影响,研究了冷却塔采用进风优化技术后冷却性能的变化。对某电厂300MW机组现场运行数据进行分析,对采用进风优化技术的冷却塔和未采用该技术的冷却塔的运行性能数据进行比较:在进风口安装导风板可削弱外界侧风的不利影响,均匀塔内通风,改善冷却塔的冷却性能。提出以温度变化相对量作为衡量和评价冷却塔在侧风下冷却性能新的技术指标,该指标也可应用于其他自然通风湿式冷却塔。 The cross-wind has a distinct influence on thermal performance of cooling towers. Air deflectors are installed around the air inlet circumference of the tower to improve the efficiency. The thermal performance of natural draft wet cooling towers of 300 MW units in a power plant is analyzed. Engineering modification is made in one tower in order to improve the cooling efficiency. The operation data of the tower are investigated and compared with that of another similar tower which is not modified. The results show that the air deflectors installed around the tower inlet can reduce the adverse effect of cross-wind, improve the flow uniformity of the inlet air and finally improve the cooling performance of the tower. In addition, a new index named the relative variation of water temperature difference is presented to evaluate and rate the performance of cooling towers subjected to cross-wind. The evaluation method is also applicable for other natural draft wet cooling towers.
出处 《中国电力》 CSCD 北大核心 2009年第10期24-27,共4页 Electric Power
关键词 导风板 侧风 技术改造 温度变化相对量 air deflector cross-wind engineering modification relative variation of water temperature difference
作者简介 作者简介:戴振会(1986-).女,山东枣庄人,硕士研究生,从事火电厂热力没备安全经济与控制的研究。E-mail:dzh0724@yahoo.com.cn
  • 相关文献

参考文献6

二级参考文献19

共引文献23

同被引文献132

引证文献14

二级引证文献74

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部