摘要
由于失电残压的存在,对感应电动机进行重合闸或备用电源再投入操作时可能会引起大的冲击电流和冲击转矩,对电源与电动机造成危害,并引发线路保护误动及电能质量下降等问题。文章通过建立空间向量下的感应电动机模型来研究失电后电动机内部的电磁变化规律,推导出了感应电动机的失电残压解析式,并分析了电机在不同时刻恢复电源时引起的冲击电流与冲击转矩。
The residual voltage of induction motor after AC dump(RVACD) may probably result in inrush current and inrush torque when induction motor was reclosed or reswitched on the alternate power source, which would damage motor or bring power source problems such as mal-operation of feeder protection and voltage sag, etc. In this paper, the space vector based model of motor is used to research the RVACD so as to thoroughly analyze the varying laws of electrical qualities and magnetic field after dumping, deduce the analytical expression of residual voltage. The inrush current and torque are analyzed for power source to be restored at different moment after dumping.
出处
《电力系统保护与控制》
EI
CSCD
北大核心
2009年第4期45-48,53,共5页
Power System Protection and Control
关键词
感应电动机
空间向量
失电残压
电源恢复
induction motor
space vector
residual voltage
power restoration
作者简介
高吉增(1983-),男,调度专工,从事继电保护与运行方式工作;E-mail:cumtyyi@126.com。
杨玉磊(1982-),男,硕士研究生,从事继电保护、电机节能控制研究;
崔学深(1973-),男,副教授,从事电力系统稳定性,电机控制与节能技术方面的研究。