安装故障限流器的输电线路潜供电弧特性与单相重合闸策略 被引量:22

Secondary Arc Characteristics and Single-phase Autoreclosure Scheme of EHV Transmission Line With Fault Current Limiter
在线阅读 下载PDF
导出
摘要 针对安装氧化锌避雷器式故障限流器的500kV输电系统,利用电磁暂态计算程序分析了限流器旁路开关不同断开时间和不同弧道电阻对潜供电流特性的影响。基于等效阻抗网络和拉普拉斯变换方法,分析了潜供电流自然振荡频率与衰减系数的变化情况,从理论上解释了潜供电流低频分量的产生机理。提出了氧化锌避雷器式故障限流器与单相自动重合闸的时序配合策略,并进行了仿真验证。仿真结果表明,该策略可有效消除可能的潜供电流低频分量对单相自动重合闸的不利影响,既能确保自动重合闸操作的正常时序,又能兼顾故障限流器的自恢复特性。 With regard to a 500 kV long-distance transmission line installed with zinc oxide surge arrester (MOA) based FCL (fault current limiter), the influence of both the FCL bypass switch operation and the different arc resistances on the characteristics of the secondary arc current was analyzed by EMTP (electromagnetic transients program) simulations. The decay factor and the oscillation frequency of the secondary arc current were computed based on the equivalent impedance network and Laplace transformation, with a view to elucidating the nature of the low frequency behavior of the secondary arc current. A time sequence coordination scheme between the single-phase autoreclosure (SPAR) and the FCL operation was proposed and verified concretely by simulations. Simulation results show that the proposed scheme can effectively eliminate the side impact caused by the low frequency current components on the SPAR, and the scheme can guarantee the normal operational sequence of a SPAR as well as the self-restoration of a FCL.
出处 《中国电机工程学报》 EI CSCD 北大核心 2008年第31期62-67,共6页 Proceedings of the CSEE
基金 山东省自然科学基金项目(Q2004F03) 山东省中青年科学家基金资助项目(2005BS01011)。
关键词 故障限流器 氧化锌避雷器 单相自动重合闸 潜供电流 fault current limiter zinc oxide surge arrester single-phase auto-reclosure secondary arc current
作者简介 刘洪顺(1981-),男,博士研究生,主要从事电力系统经济型故障限流器的研究工作,hongshun1981@mail.sdu.edu.cn; 李庆民(1968-),男,教授,博士生导师,主要从事新型高压电器方面的科学研究工作; 邹亮(1983-),男,博士研究生,主要从事电力系统经济型故障限流器的研究工作。
  • 相关文献

参考文献15

二级参考文献92

共引文献282

同被引文献254

引证文献22

二级引证文献180

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部