期刊文献+

一种新的三相光伏并网系统孤岛检测方法 被引量:1

A new technique on islanding detection of three-phase grid-connected photovoltaic inverter
在线阅读 下载PDF
导出
摘要 基于三相光伏并网逆变器论述了反孤岛效应策略,同时,为了进一步缩小不可检测区(NDZ)的范围,提出了一种正反馈频率偏移法与正反馈电压偏移法相结合的孤岛检测方法,并阐述了该方法的原理。利用Matlab/Simulink软件对其进行了系统建模与仿真研究,并根据仿真结果搭建测试电路,对并网逆变器的反孤岛控制能力进行了测试,实现了非检测区域的进一步减小。实验结果表明,该方法在100 ms内可有效地检测出系统的孤岛状态。 Based on the three-phase grid-connected photovoltaic inverter, the anti-lsland protection strategy was discussed. In order to reduce the non-detection zone (NDZ) , a new frequency drift with voltage drift technique was proposed. The simulation model of system was established in Matlab/Simulink, and the experiment was researched according to the simulation, the reduction of NDZ was realized. The experimental results prove that the islanding can be detected effectively within 100 milliseconds by new technique.
出处 《机电工程》 CAS 2008年第9期34-36,50,共4页 Journal of Mechanical & Electrical Engineering
关键词 孤岛检测 频率偏移 电压偏移 不可检测区 islanding detection frequency drift voltage drift non-detectlon zone(NDZ)
作者简介 薄涛(1984-),男,山西太原人,主要从事电力电子与电力传动方面的研究。
  • 相关文献

参考文献4

  • 1RANADE S J, PRASAD R, OMICK S, et al. A study of islanding in utility-connected residential photovoltaic systems [ J ]. IEEE Transactions on Energy Conversion, 1989,9 (9) :436 -445.
  • 2禹华军,潘俊民.并网发电逆变系统孤岛检测新方法的研究[J].电力系统及其自动化学报,2005,17(5):55-59. 被引量:55
  • 3YE Zhi-hong, KOLWALKAR A, ZHANG YU, et al. Evaluation of anti-islanding schemes based oll nondetection zone concept[ J] . IEEE Transactions on Power Electronics, 2004,19(5) :1171 - 1176.
  • 4JUNG Y, CHOI J, YU B, et al. A Novel Active Frequency Drift Method of Islanding Prevention for the grid-connected Photovoltaic Inverter [ C ]//Power Electronics Specialists Conference,2005 ( PESC'05 ). Brazili [ s. n. ] , 2005 : 1915 - 1921.

二级参考文献4

  • 1Hung Guokiang,Chang Chihchang,Chen Chernlin.Automatic phase-shift method for islanding detect-ion of grid-connected photovoltaic inverters[J].IEEE Trans on Energy Conversion,2003,18(1):169-173.
  • 2IEEE Std 929-2000,IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems[S],Institute of Electrical and Electronics Engineers,Inc,New York,USA,2000.
  • 3Ghali F M A.A combined technique for elimination of islanding phenomenon[A].In:Proceedings of the 25th IEEE Photovoltaic Specialists Conference[C].Washington,D C:1996,1473-1476.
  • 4Ropp M E,Begovic M,Rohatgi A.Analysis and per-formance assessment of the active frequency drift method of islanding prevention[J].IEEE Trans on Energy Conversion,1999,14(3):810-816.

共引文献54

同被引文献9

  • 1ZEINELDIN H H,EI-SAADANY E F,SALAMA M M. Impact of DG interface control on islanding detection and non-detection zones[J].IEEE Transactions on Power Delivery,2006,(03):1515-1523.doi:10.1109/TPWRD.2005.858773.
  • 2ROPP M E,BEGOYIC M,ROHATGI A. Analysis and performance assessment of the active frequency drift method of islanding prevention[J].IEEE Transaclions on Energy Conversion,1999,(03):810-816.doi:10.1109/60.790956.
  • 3DOUMBIA M L,AGBOSSOU K. Islanding Protection Evaluation of Inverter-based Grid Connected Hybrid Fenewable Energy Systems[A].Canadian,2004.1081-1084.
  • 4LOPES L A C,SUN Hui-li. Performance assessment of active frequency drifting islanding detection methods[J].IEEE Transactions on Energy Conversion,2006,(01):171-180.doi:10.1109/TEC.2005.859981.
  • 5YE Zhi-hong,KOWALKAR A,ZHANG Yu. Evaluation of anti-Islanding schemes based on non-detection zone concept[J].IEEE Transactions on Power Electronics,2004,(05):1171-1176.doi:10.1109/TPEL.2004.833436.
  • 6刘芙蓉,康勇,段善旭,王志峰,王辉.主动移频式孤岛检测方法的参数优化[J].中国电机工程学报,2008,28(1):95-99. 被引量:99
  • 7刘方锐,康勇,张宇,段善旭.带正反馈的主动移频孤岛检测法的参数优化[J].电工电能新技术,2008,27(3):22-25. 被引量:29
  • 8邓燕妮,桂卫华.一种低畸变的主动移频式孤岛检测算法[J].电工技术学报,2009,24(4):219-223. 被引量:40
  • 9相海涛,戴卫力,蒋海江,严仰光.主动频率漂移法孤岛效应检测分析与优化[J].河海大学学报(自然科学版),2010,38(2):231-235. 被引量:4

引证文献1