期刊文献+

世博会展馆内的空气微生物污染控制 被引量:4

Study on Treatment of Air Microorganism Pollution in Exhibition Halls of World Expo
在线阅读 下载PDF
导出
摘要 文章研究了世博会展馆内空气微生物污染的控制问题。研究表明,参观人数为400人/小时的情况下,展馆内微生物气溶胶产生量达到44000 cfu/h.m3。空调过滤系统若采用中效过滤,展馆内空气微生物浓度可至4406 cfu/m3,仍超过《室内空气质量标准》2500 cfu/m3的浓度限值,需使用消毒技术净化展馆内空气。增加中效过滤器能够有效去除可吸入颗粒物,有助于降低室内空气微生物浓度。 This paper studied treatment of air microorganism pollution in exhibition halls of the World Exposition. If the visitor current were 400 people per hour, the production rate of microorganism aerosol would be 44000 cfu/h · m^3. If medium effect air filters was adopted in centralized air conditioning system, the content of air microorganism would be 4406 cfu/m^3. It was still higher than the "Quality Standard of Room Air" (2500 cfu/m^3 ) , so air disinfection technology must be utilized. The research indicated that increase of medium effect air filter could reduce the content of microorganism in room air.
作者 梅娟 赵由才
出处 《四川环境》 2008年第2期120-122,126,共4页 Sichuan Environment
基金 上海市科学技术委员会国际合作项目(062307038)
关键词 世博会 空气微生物 集中空调 World Expo air microorganism pollution centralized air conditioning system
作者简介 梅娟(1976-),女。山东枣庄人,同济大学环境工程专业2006级在读博士研究生,讲师,主要从事城市生态和环境保护方面的教学和研究。
  • 相关文献

参考文献4

二级参考文献32

  • 1边藏丽,杨远荣,熊贻该,杨代玉.激光杀菌的试验研究[J].中国消毒学杂志,1995,12(3):168-168. 被引量:2
  • 2邓慧华,陆祖宏.半导体光催化杀菌的机理和应用[J].东南大学学报(自然科学版),1996,26(6):1-6. 被引量:19
  • 3Shakun W. The causes and control of mold and mildew in hot and humid climates. ASHRAE Transactions, 1992, 98(1):1282-1292.
  • 4Tenwolde A. Steady-state one-dimensional water vapor movement by diffusion and convection in a multilayered wall.ASHRAE Transactions, 1985,91 (1A) : 322- 342.
  • 5Lotz W A. Moisture problems in buildings in hot humid climates. ASHRAE Journal, 1989,31(4):26-27.
  • 6Carpenter S. Waterloo region green home. ASHRAE Journal,1996,38(10):43-46.
  • 7Gottfried D A. Green building environmental control: a case study. Heating/Piping/Air Conditioning, 1997,69 (2) : 71 - 78.
  • 8Molhave L. Volatile organic compounds, indoor air quality, and health. Indoor Air, 1991,(1):357-376.
  • 9Furuhashi M. Efficiency of bacterial filtration in various commercial air filters for hospital air conditioning [ J ]. Bull Tokyo Med Dent Univ, 1978; 25(3) :147.
  • 10Brickner PW, Vincent RL, First M, et al. The application of ultraviolet germicidal irradiation to control transmission of airborne disease: biotenorism countermeasure [ J ]. Public Health Rep,2003; 118(2): 99.