期刊文献+

珠海电厂FGD烟气系统的防腐设计及存在问题处理措施 被引量:3

Anticorrosion Design and Existing Problems Handling Measures of FGD Flue Gas System in Zhuhai Power Plant
在线阅读 下载PDF
导出
摘要 介绍了珠海电厂2×700MW燃煤机组石灰石/石膏湿法(FGD)烟气系统的防腐设计,对运行过程中出现的问题,如原烟道腐蚀、衬胶鼓泡及玻璃鳞片涂层开裂等原因进行了详细的分析,并提出了采用单独配置密封风机、调整密封片间隙、重新防腐等措施,修复检查结果合格。建议要重视烟气系统防腐工序,进一步改善脱硫设备的结构设计。 The paper briefed the flue gas system anticorrosion design of limestone/gypsum wet method FGD of 2 × 700 MW coal-fired units in Zhuhai power plant,analyzed in detail the occurring problems in operation such as the corrosion of original flue gas ducts,buldging of rubber coating and fracturing of glass scale coating etc.causes,and put forward:to adopt the draft fans with sealings,to adjust the clearances of sealings and to conduct preventive anticorrosion once again etc. measures. The renovation result was up to standard.The paper also suggested,to attach importance to anticorrosion procedures of flue gas system and to further improve the configuration design of desulfurization equipment.
作者 张雪莲 郑楷
出处 《电力设备》 2008年第3期48-51,共4页 Electrical Equipment
关键词 发电厂 设计工艺 烟气脱硫 烟气系统 防腐 flue gas desulfurization(FGD) design technology flue gas system anticorrosion
作者简介 张雪莲(1981-),女,助理工程师,从事环保工程技术工作; 郑楷(1976-),女,讲师,硕士,从事基础理论和专业理论的教学和研究工作。
  • 相关文献

参考文献2

二级参考文献3

  • 1[2]ASTM F 607-2003,衬垫材料黏结到金属表面的黏附性的标准试验方法[S].2003.
  • 2[3]SH涂料检测报告[R].濮阳市质检中心.2005.
  • 3曾庭华,杨华,马斌,等.湿法烟气脱硫系统的安全性及优化[M].北京:中国电力出版社,2003.

共引文献7

同被引文献17

引证文献3

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部