摘要 列举了天生桥—广州直流输电系统、三峡—广东鹅城直流输电系统、贵州高坡—广东肇庆直流输电系统调试投运期间的大量现场实测数据,并对这些数据进行分析,结果表明直流输电系统单极大地回线方式或双极不对称方式运行时对交流系统中性点接地运行变压器的噪声、变压器中性线直流电流以及电网谐波电压均会产生较大影响,严重时可能损坏电力设备。该结论对直流输电系统的设计、建设、运行以及交流系统采取相应措施有极重要的参考价值。 This paper lists a mass of field test data during the commissioning of the three high voltage direct current (HVDC) transmission systems of Tianshengqiao-Guangzhou, the Three Gorges-Echeng in Guangdong, and Gaopo in Guizhou- Zhaoqing in Guangdong. The analysis of these data shows that the monopolar ground circuit operation mode or the bipolar asymmetric mode of HVDC transmission system has great impact on the noise and neutral line direct current of transformers with earthed neutral point and the harmonic voltage of the AC system, and is likely to damage power equipment in serious cases. This conclusion has vital referential value to the design, construction and operation of HVDC system as well as the adoption of corresponding measures for AC system.
出处 《广东电力》 2006年第1期1-7,共7页 Guangdong Electric Power
关键词 直流输电 单极大地回线方式 变压器 噪声 直流偏磁 谐波 direct current transmissiom monopolar ground circuit operation mode transformer noise direct current magnetic biasing harmonic
作者简介 梅桂华(1963-),男,湖北孝感人,电力系统分析高级工程师,工学硕士.主要从事电力系统分析工作。
  • 相关文献

参考文献5

  • 1浙江大学发电教研组直流输电科研组.直流输电[M].北京:电力工业出版社,1982..
  • 2广东省电力试验研究所.天广直流输电对广东省电网变压器运行噪声影响测试报告(2001年1月12日)[R].广州:广东省电力试验研究所,2001..
  • 3广东省电力试验研究所.天广直流输电对广东省电网变压器运行噪声影响测试报告(2004年2月20日)[R].广州:广东省电力试验研究所,2001..
  • 4广东省电力试验研究所.三广直流输电对交流系统的影响测试报告[R].广州:广东省电力试验研究所,2004..
  • 5广东省电力试验研究所.贵广直流单极大地方式对变压器的影响测试简报[R].广州:广东省电力试验研究所,2004..