期刊文献+

基于S注入法的自闭贯通线路故障定位系统 被引量:8

Fault Location System for Automatic Block and Continuous Transmission Lines Based on S-Injection Method
在线阅读 下载PDF
导出
摘要 将S注入法和无线传输节点相结合,利用传感器网络的自组网功能以及高容错性构建了无线节点通信网络.提出了采用传感器网络技术的铁路自闭贯通线故障定位系统. 该系统由信号注入装置、无线节点、开关站无线处理单元和智能故障信息处理系统构成.通过无线节点检测注入信号.智能故障信息处理系统接收无线节点传来的检测结果,并判断故障位置.注入信号的电源为恒流源,频率范围为220~320 Hz.设计了并列方式和交错方式两种检测节点的布置方案.这两种方式均能满足信息传输可靠性的要求,但并列方式的系统可靠性比交错方式提高了2倍.该系统定位精度可根据需要调整. A wireless-node communication network was designed to detect single-phase-to-ground faults in railway automatic blocking and continuous transmission lines by combining S-injection method with wireless nodes. The system makes use of automatic net-organization function and high fault- tolerant characteristic of sensor networks. It is composed of a signal injection device, wireless nodes, a wireless process unit at the switch station and an intelligent fault detection system. Signals are injected on a wireless node. The intelligent fault detection system receives the detected results transmitted from the wireless node and locate the fault position. Determined by simulations, the power source is of constant current and its frequency ranges from 220 to 320 Hz. The sensors are arranged in two modes: parallel and interleaving. These two modes both meet the requirement of reliability for information transmission, but the reliability of the former is as triple as that of the latter. The locating precision of the system is adiustable according to application.
出处 《西南交通大学学报》 EI CSCD 北大核心 2005年第5期569-574,共6页 Journal of Southwest Jiaotong University
基金 国家自然科学基金资助项目(50407009) 教育部科学技术重点研究项目(104163)
关键词 自闭贯通线路 小电流接地系统 注入法 故障定位 传感器网络 automatic block and continuous transmission line small current neutral grounding system S-injection method fault location wireless sensor network
作者简介 何正友(1970-),男,教授,博士,博士生导师,研究方向为小波分析在电力系统中的应用与配电自动化.
  • 相关文献

参考文献9

二级参考文献88

  • 1何正友,王志兵.铁路自闭贯通线路故障检测模型[J].西南交通大学学报,2004,39(4):451-454. 被引量:10
  • 2[1]Toshihisa Funabashi.Digital fault location high resistance grounded transmission Lines[J].IEEE Trans.Power Delivery.1999,14(1):80-85.
  • 3[2]Johns A T Whittard.New technique for the accurate location of earth faults on transmission system[J].IEE Proc.-Gener.Transm.Distrib..1999,142 (2):73-79.
  • 4[3]Magnago Fernando H.Fault location using wavelets[J].IEEE Trans.Power Delivery.1998,13:1475-1481.
  • 5[4]Bo Z Q.Accurate fault location technique for distribution system using fault-generated high-frequency transient voltage signals[J].IEE Proc.-Gener.Transm.Distrib..1999,146 (1):73-79.
  • 6ALERT. http://www.altersystem.org.
  • 7Bonnet P, Gehrke J, Seshadri P. Querying the physical world. IEEE Personal Communication, 2000,7(5):10-15.
  • 8Noury N, Herve T, Rialle V, Virone G, Mercier E. Monitoring behavior in home using a smart fall sensor. In: Proceedings of the IEEE-EMBS Special Topic Conference on Microtechnologies in Medicine and Biology. Lyon: IEEE Computer Society, 2000.607~610.
  • 9Sensor Webs. http://sensorwebs.jpl.nasa.gov/.
  • 10Shill E, Cho S, Ickes N, Min R, Sinha A, Wang A, Chandrakasan A. Physical layer driven protocol and algorithm design for energy-efficient wireless sensor networks. In: Proceedings of the ACM MobiCom 2001. Rome: ACM Press, 2001. 272-286.

共引文献2514

同被引文献65

引证文献8

二级引证文献37

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部