过热度变化对制冷系统性能影响的仿真与试验研究 被引量:22

Simulative and Experimental Studies on the Effect of Superheat Degree on the Refrigeration System Performance
在线阅读 下载PDF
导出
摘要 运用模型仿真和试验验证手段对具有典型意义的风冷螺杆热泵机组进行过热度变化对机组性能影响的深入研究,仿真和实验都揭示出过热度变化对制冷系统性能的影响规律。同时试验也表明:样机蒸发器出口过热度从10℃变为2℃时,系统制冷量增加13.4%,COP值增加9.3%,而输入功率只增加4%。可见通过采用电子膨胀阀降低蒸发器出口过热度对系统性能有较大的提高。 Model simulation and experiments are carried out to investigate the effect of superheat degree on the performance of Air Cooled Screw Heat Pump. Both simulative and experimental results reveal the relations between superheat degree and performance characteristics. Furthermore, The experimental result shows that change of superheat degree at the outlet of the evaporator from 10℃ to 2℃ will cause 13.4% increase in cooling capacity and 9.3% increase in COP, but only 4% increase in power consumption. It is easily obtained that using electronic expansion valve to decrease the superheat degree could improve the system performance remarkably.
机构地区 东南大学
出处 《流体机械》 CSCD 北大核心 2005年第9期43-47,共5页 Fluid Machinery
关键词 电子膨胀阀 热力膨胀阀 风冷螺杆热泵 过热度 制冷系统 electronic expansion valve thermal expansion valve air source heat pump superheat degree refrigeration system
作者简介 梁彩华(1979-),男,博士研究生,通讯地址:210096江苏南京市东南大学动力工程系。
  • 相关文献

参考文献12

  • 1谈磊,陆震,范林.风冷式热泵机组应用中电子膨胀阀与热力膨胀阀的比较[J].制冷技术,2001,21(4):22-24. 被引量:12
  • 2孙文哲,周永明,陈芝久,于兵.膨胀阀性能对比的实验研究[J].流体机械,1998,26(8):51-55. 被引量:3
  • 3Aprea Ciro ,Rita Mastrullo.Experimental evaluation of electronic and thermostatic expansion valves performances using R22 and R407C[J].Applied Thermal Engineering,,22 (2002):205-218.
  • 4Choi J M, Kim Y C.Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves[J].Energy ,28 (2003):141-155.
  • 5Hewitt N J,et al.Comparison of Expansion Valve Performance[J].Inter.J.EnergyResearch,1995,19:347-359.
  • 6Thuesen S E,et al.Improved control of liquid in-jection into display case evaporators, 1985(91), Part1 A, No2861:80-91.
  • 7Hewitt N J, et al.Comparison of Expansion Valve Performance[J].Inter.J.EnergyResearch,1995,19:347-359.
  • 8梁彩华,张小松,巢龙兆,刘一民.显热除霜方式与逆向除霜方式的对比试验研究[J].制冷学报,2005,26(4):20-24. 被引量:31
  • 9Dittus F W,Boelter L M K.Heat transfer in single phase for plate finned tube heat exchangers[A]. In: Proceedings of the 5th International Heat Transfer Conference[C].SanFrancisco,1980,2275-2280.
  • 10Dobson M K, Chato J C. Heat transfer and flow regimes during condensation in horizontal tubes[J]. ACRC Trans, 1994:57-61.

二级参考文献16

  • 1韩慧秋,董威.空气源热泵机组除霜问题分析[J].长春工程学院学报(自然科学版),2003,4(1):14-16. 被引量:2
  • 2姚杨,马最良.空气源热泵冷热水机组室外换热器结霜工况下数学模型的建立[J].流体机械,2001,29(10):50-52. 被引量:12
  • 3白梓运,陈芝久.电子膨胀阀及其在蒸发器过热度自适应控制中的应用[J].暖通空调,1996,26(2):21-24. 被引量:38
  • 4Yoshinobu Yamazaki. Inverter Air-Conditioners with Thermal Storage Unit and Fuzzy Logic Control System.REFRIGERATION, 1992,67(772):14-22.
  • 5Masami Hayashi,Shigeru Nariai,Masaya Hayama.Develoment of Scroll Inverter Air Conditioners,REFRIGERTION, 1992,67(772):,51-57.
  • 6Watters Richard J O'Neal, Dennis L Yang, Jianxin. Effect of fin staging on frost/defrost performance of a two-row heat pump evaporator at standard test conditions. 2001,107(2):240-249.
  • 7Finstad, Clint Mei V C Chen, F C et al. Warm liquid defrosting for supermarket refrigerated display cases. ASHRAE Transactions, 2002,108 (1):669-672.
  • 8Elovitz, Kenneth Behr, John Hrnjak P S et al . Defrost issues in indirectly refrigerated display cases. ASHRAE Transactions,2001,107 (2):466-472.
  • 9Mago, Pedro J Al-Mutawa, Nawaf K Theen et al. Psychrometrics in the supersaturated frost zone. ASHRAE Transactions, 2001.107 (2):753-767.
  • 10朱瑞琪,陈文勇,吴业正.电子膨胀阀的控制[J].流体机械,1998,26(5):20-25. 被引量:25