期刊文献+

光纤复合架空地线(OPGW)雷击试验分析 被引量:15

Lightning Test and Analysis for Optical Fiber Composite Overhead Ground Wires
在线阅读 下载PDF
导出
摘要 按照IEC60794和DL/T832标准,对不同参数类型的OPGW进行了雷击试验,分析总结了OPGW外层绞线单丝直径、绞线材料、雷击转移电荷库仑数、张力、雷电参数等对OPGW雷击断股的影响。在此基础上提出,采用较大直径外层绞线和铝包钢材料外层绞线的OPGW可有效防止其遭雷击断股。 According to IEC 60794 and DL/T 832 standards, lightning tests are taken on OPGW samples with different types and parameters. The influences of diameter and material of outer-layer strands, electric charge quantity of lightning, strength and lightning parameters on the break of OPGW outer-layer strands caused by lightning are discussed and analyzed. Based on this, in order to prevent the break of out-layer strands caused by lightning, OPGWs with bigger diameter and ACS material outer-layer strands are preferred.
出处 《高电压技术》 EI CAS CSCD 北大核心 2005年第5期7-9,共3页 High Voltage Engineering
关键词 OPGW 雷击 断股 试验分析 OPGW lightning broken strand test analysis
  • 相关文献

参考文献5

  • 1IEC60974—4-1—1997.光纤复合架空地线[S].[S].,..
  • 2DL/T832-2003.光纤复合架空地线[S].[S].,..
  • 3Anderson R B,Eriksson A J.Lightning parameters for engineering applications[C].CIGRE Study Committee 33 Overvoltage and Insulation COordination.[s.l],1979.
  • 4Schank W Z,Wiesinger J.Damages to optical ground wires caused by lightning[C].10th International Symposium on High Voltage Engineering.[s.l.],1997.
  • 5胡毅,易辉,王力农,张俊兰.光纤复合架空地线雷击断股的分析及试验[J].电力系统通信,2003,24(5):14-15. 被引量:10

二级参考文献2

  • 1.GB/T 8999—1999.光复合架空地线[S].,1999..
  • 2IEC 60 94-4- 1 - 1999.Optical Fibre Cables Part4 - I :Aerial Optical Cables for High-Voltage Power Line[S] .1999.