一起500kV交流滤波器断路器故障分析 被引量:3

Analysis of a 500kV AC Filter Circuit Breaker Fault
原文传递
导出
摘要 本文对兴仁换流站500kV 572交流滤波器断路器断开故障这一事件进行了分析和研究。通过解体发现断路器动静触头击穿,动静触指变形以及均压铜罩铆钉脱落等情况,找到了事故原因和解决方案。本案例可为设备监造、现场检修和运行维护人员提供借鉴。 This paper makes an analysis and research for the event that 500kV 572AC filter circuit breaker unsuccessful switch off in Xinren converter station.After disassembly of the fault circuit breaker,some faults were found that the moving contact and break-back contact did dielectric puncture,that break-back contact of fingers did subsequent distortion,and that rivets on the equalizing copper shield did shed.According to the study of above,the reason and solution of this incident were taken in this thesis.It hopes to provide a reference to user and operators.
作者 甘鹏 张杰
出处 《水电自动化与大坝监测》 2013年第5期75-77,86,共4页 HYDROPOWER AUTOMATION AND DAM MONITORING
关键词 交流滤波器 断路器 均压铜罩 铆钉 分析 AC filter circuit breaker rivet equalizing copper shield analysis