摘要
To a kind of centrifugal water chiller with R22 and about 1 745 kW of cooling capacity,a heat exchanger was added between the outlet of compressor and original condenser to get part of or all the condensing heat.Condensing heat can be recovered by compound condensing method,which adopts air-cooling model +water-cooling model or water-cooling model +water-cooling model at the condensing side of the system.By exergy analysis and experiment research on compound condensing heat recovery of centrifugal chiller,the results are obtained that the capability of the whole system increases,the energy efficiency ratio(EER)becomes 3.2~5.0 from 2.2~3.4,which implies the EER increases about 1.0~1.5,the exergy efficiency increases about 10%,and the chiller runs more stably after reformation.
To a kind of centrifugal water chiller with R22 and about 1 745 kW of cooling capacity,a heat exchanger was added between the outlet of compressor and original condenser to get part of or all the condensing heat.Condensing heat can be recovered by compound condensing method,which adopts air-cooling model +water-cooling model or water-cooling model +water-cooling model at the condensing side of the system.By exergy analysis and experiment research on compound condensing heat recovery of centrifugal chiller,the results are obtained that the capability of the whole system increases,the energy efficiency ratio(EER)becomes 3.2~5.0 from 2.2~3.4,which implies the EER increases about 1.0~1.5,the exergy efficiency increases about 10%,and the chiller runs more stably after reformation.
出处
《湖南大学学报(自然科学版)》
EI
CAS
CSCD
北大核心
2009年第S1期123-126,共4页
Journal of Hunan University:Natural Sciences
基金
Supported by National"863"Plan(2006AA05Z229)