This paper presents a method of tuning governor control parameters of an isolated hydropower generator considering the primary frequency performance and small-signal stability. First, generators that can be operated i...This paper presents a method of tuning governor control parameters of an isolated hydropower generator considering the primary frequency performance and small-signal stability. First, generators that can be operated in isolated state are identified. Second, different schemes are proposed for generator mode switching from on-grid to off-grid state through comparison and mechanism analysis. Third, the time domain model and frequency domain model of the isolated generator governor are constructed to respectively estimate the primary frequency performance and small signal stability. Parameter sets that satisfy the primary frequency performance and small signal stability are acquired as optimal values of governor control parameters. Finally, the measurement-based parameters of the governor are identified and validated using simulations to demonstrate the feasibility and effectiveness of the method.展开更多
基金supported by the Fujian Provincial Government Project (Title: Research on whole process evaluation of dynamic stability and control strategy in condition of grid connection of ultra-high voltage and large scale penetration of nuclear power.No.2015H0023)the State Grid Science & Technology Project (Title: Research on the improvement on stability of primary frequency of generator in account of the tolerance of equipment.No.52130417002P)the Key project of State Grid Fujian Electric Power Company,Ltd (research on key technologies of primary frequency power oscillation mechanism analysis and inhibition measures in large-scale unit in Fujian power grid.No.52130417000J)
文摘This paper presents a method of tuning governor control parameters of an isolated hydropower generator considering the primary frequency performance and small-signal stability. First, generators that can be operated in isolated state are identified. Second, different schemes are proposed for generator mode switching from on-grid to off-grid state through comparison and mechanism analysis. Third, the time domain model and frequency domain model of the isolated generator governor are constructed to respectively estimate the primary frequency performance and small signal stability. Parameter sets that satisfy the primary frequency performance and small signal stability are acquired as optimal values of governor control parameters. Finally, the measurement-based parameters of the governor are identified and validated using simulations to demonstrate the feasibility and effectiveness of the method.