Considering the existing problems of current Thevenin equivalent algorithms,a tracing algorithm of Thevenin equivalent that is applicable to power systems with large disturbance is presented.First,the potential voltag...Considering the existing problems of current Thevenin equivalent algorithms,a tracing algorithm of Thevenin equivalent that is applicable to power systems with large disturbance is presented.First,the potential voltage amplitude of Thevenin equivalent at the moment of fault is calculated with the parameters before fault.Then the resistance before fault and the potential voltage amplitude of the moment of fault is used to calculate other parameters of the moment of fault.The main steps of this algorithm are as follows:1)The resistance and reactance of Thevenin equivalent before fault are used as initial parameters.展开更多
文摘Considering the existing problems of current Thevenin equivalent algorithms,a tracing algorithm of Thevenin equivalent that is applicable to power systems with large disturbance is presented.First,the potential voltage amplitude of Thevenin equivalent at the moment of fault is calculated with the parameters before fault.Then the resistance before fault and the potential voltage amplitude of the moment of fault is used to calculate other parameters of the moment of fault.The main steps of this algorithm are as follows:1)The resistance and reactance of Thevenin equivalent before fault are used as initial parameters.