摘要
分析了地震后支柱绝缘子的缺陷特征,对震后支柱瓷绝缘子进行现场检测,得到了地震位置与时间变化对缺陷影响的规律。结果表明:1)地震引发的故障缺陷以裂纹为主,发生在瓷套根部区域;2)支柱绝缘子缺陷数目随着与震中距离呈现下降趋势;3)瓷体中的微裂纹会随着时间的推移逐步扩大成显性裂纹。研究成果为支柱瓷绝缘子震后处理提供技术支撑。
The fault characteristics of post-earthquake post insulators were analyzed, and the rule of the influence of seismic position and time change on defects was obtained by means of field detection to the post-earthquake porcelain post insulator. The results showed that: 1) the fault and defect caused by the earthquake is mainly crack, and occurred in the contact part; 2) the number of post insulator defects decreases with the distance from the epicenter distance; 3) the microcrack in the porcelain body will gradually expand into dominant crack over time. The research results provide technical support for post-earthquake treatment of porcelain post insulator.
作者
韩晓言
蔡炜
邓鹤鸣
曹永兴
吴驰
范少君
HAN Xiaoyan;CAI Wei;DENG Heming;CAO Yongxing;WU Chi;FAN Shaojun(State Grid Sichuan Electric Power Co. Ltd, Chengdu 610041, China;NARI Group Co. Ltd. Nanjing 211000, China;Wuhan NARI Limited Liability Company, State Grid Electric Power Research Institute, Wuhan 43007, China;Electric Power Research Institute of State Grid Sichuan Electric Power Co. Ltd, Chengdu 610041, China;Liangshan Power Supply Company of State Grid Sichuan Electric Power Co. Ltd, Xichang 615000)
出处
《电瓷避雷器》
CAS
北大核心
2018年第3期144-148,共5页
Insulators and Surge Arresters
关键词
支柱绝缘子
地震破坏
震后检测
变电站
瓷体
法兰
post insulator
earthquake damage
post-earthquake detection
substation
porcelain
flange
作者简介
韩晓言(1965-),男,高级工程师,从事电网防灾减灾技术工作。