摘要
雷害事故是影响深圳地区输电线路安全运行的主要问题,在线路"易击段"安装线路避雷器,可以提高架空线路耐雷水平。简要介绍了线路避雷器的发展情况及基本原理,总结了氧化锌线路避雷器近几年在深圳电网110kV、220kV输电线路的运行经验;分析了线路避雷器降低线路雷击跳闸率的效果;讨论了线路避雷器的选点安装和运行维护等方面的问题,并提出了建议。
Lightning disturbance is a main problem that influences the operation safety of the transmission lines in Shenzhen area. Installation of line metal-oxide arrester (MOA) on transmission section with frequent lightning can improve the lightning withstand level of the transmission lines. The development and basic principle of MOA are introduced. The operation experience of MOA application in 110 kV and 220 kV transmission lines in Shenzhen power network in recent years is summarized, the effect on reducing lightning stroke tripping rate is analyzed, The site-selection, installation and maintenance of MOA are discussed, existing issues in adopting MOA and proposals are presented.
出处
《南方电网技术》
2008年第6期92-95,共4页
Southern Power System Technology
关键词
线路避雷器
输电线路
雷击
metal-oxide arrester
transmission line
lightning stroke
作者简介
魏前虎(1977-),男,工程师,学士,从事输电线路管理及高压电力电缆应用技术研究工作。Email:chongchong.er@163.com。
邓世聪(1981-),男,助理工程师,学士,从事输电线路技术管理及高压绝缘检测试验工作。
曹宁(1982~),男,助理工程师,学士,现从事输电线路运行管理工作。